background image
Pump Specifications
250 Series Submersible
Sump / Effluent Pump
0
5
10
15
20
0
10
20
30
40
50
GALLONS PER MINUTE
T
O
T
A
L HEAD
I
N
F
EET
-1
0
1
2
3
4
5
6
0.0
0.5
1.0
1.5
2.0
2.5
3.0
LITERS PER SECOND
T
O
TA
L H
E
A
D
I
N
M
E
TE
R
S
250_P1 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
background image
250-Series Dimensional Data
250_P2 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
background image
250-Series Electrical Data
MODEL HP
VOLTAGE
PHASE
FULL
LOAD
AMPS
LOCKED
ROTOR
AMPS
THERMAL
OVERLOAD
TEMP
STATOR
WINDING
CLASS
CORD
LENGTH
FT
DISCHARGE AUTOMATIC
250
1/3
115
1
5.2
8
120°C / 248°F
B 10 1
1/2
NO
MANUAL
250-2 1/3 115
1 5.2 8 120°C / 248°F
B 25 1
1/2
NO
MANUAL
251 1/3
115 1 5.2 8 120°C / 248°F
B
10
1 1/2
YES
INTEGRAL
FLOAT
251-2 1/3 115
1 5.2 8 120°C / 248°F
B 25 1
1/2
YES
INTEGRAL
FLOAT
253 1/3
115 1 5.2 8 120°C / 248°F
B 10 1
1/2
YES
PIGGY BACK
FLOAT
253-2 1/3 115
1 5.2 8 120°C / 248°F
B 25 1
1/2
YES
PIGGY BACK
FLOAT
257 1/3
115 1 5.2 8 120°C / 248°F
B 10 1
1/2
YES
INTEGRAL
VERTICLE
FLOAT
257-2 1/3 115
1 5.2 8 120°C / 248°F
B 25 1
1/2
YES
INTEGRAL
VERTICLE
FLOAT
250-Series Technical Data
IMPELLER
VORTEX ENGINEERED
POLYMER
SOLIDS HANDLING SIZE
½"
PAINT
POWDER COAT
MAX LIQUID TEMP
60°C 140°C
MAX STATOR TEMP
CLASS B
130°C/ 266°F
THERMAL OVERLOAD
120°C / 248°F
POWER CORD TYPE
SJTW
MOTOR HOUSING /
VOLUTE
CLASS 25 CAST IRON
SHAFT
STAINLESS
HARDWARE
STAINLESS
ORINGS
BUNA N
MECHANICAL SEAL
UNITIZED CERAMIC
CARBON
WEIGHT
23 LBS
250_P3 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
background image
250-Series Specifications
1.01 GENERAL:
The contractor shall provide labor, material, equipment, and incidentals required to provide (QTY) centrifugal pumps as
specified herein. The pump models covered in this specification are Series 250 single phase pumps. The pump furnished for this
application shall be model ______________as manufactured by Liberty pumps.
2.01 OPERATING CONDITIONS:
Each submersible pump shall be rated at 1/3 hp, 115 volts, single phase, 60 Hz., 3450 RPM. The unit shall produce
______G.P.M. at ______ feet of total dynamic head.
The submersible pump shall be capable of handling effluent with 1/2" solid handling capability. The submersible pump shall have
a shut-off head of 18 feet and a maximum flow of 42 GPM @ 5 feet of total dynamic head.
The pump shall be controlled with:
______A piggy back style on/off float switch.
______An integrally wired on/off float switch.
______A Vertical Mechanical Float (VMF) type on/off switch.
______A NEMA 4X outdoor simplex control panel with three float switches and a high water alarm.
______A NEMA 1 indoor simplex control panel with three float switches and a high water alarm.
______A NEMA 4X outdoor simplex control panel with four float switches and a high water alarm.
______A NEMA 1 indoor simplex control panel with four float switches and a high water alarm.
______A NEMA 4X outdoor duplex control panel with three float switches and a high water alarm.
______A NEMA 1 indoor duplex control panel with three float switches and a high water alarm.
______A NEMA 4X outdoor duplex control panel with four float switches and a high water alarm.
______A NEMA 1 indoor duplex control panel with four float switches and a high water alarm.
3.01 CONSTRUCTION:
Each centrifugal effluent pump shall be equal to the
certified Series 250 SERIES pumps as manufactured by Liberty
Pumps, Bergen NY. The castings shall be constructed of class 25 cast iron. The motor housing shall be oil filled to dissipate heat.
Air filled motors shall not be considered equal since they do not properly dissipate heat from the motor. All mating parts shall be
machined and sealed with a Buna-N o-ring. All fasteners exposed to the liquid shall be stainless steel. The motor shall be
protected on the top side with sealed cord entry plate with molded pins to conduct electricity eliminating the ability of water to enter
internally through the cord. The motor shall be protected on the lower side with a unitized ceramic/carbon seal with stainless steel
housings and spring. The pump shall be furnished with stainless steel handle.
4.01 ELECTRICAL POWER CORD
The submersible pump shall be supplied with 10 or 25 feet of multiconductor power cord. It shall be cord type SJTW, capable of
continued exposure to the pumped liquid. The power cord shall be sized for the rated full load amps of the pump in accordance
with the National Electric Code. The power cable shall not enter the motor housing directly but will conduct electricity to the motor
by means of a water tight compression fitting cord plate assembly, with molded pins to conduct electricity. This will eliminate the
ability of water to enter internally through the cord, by means of a damaged or wicking cord.
250_P4 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
background image
5.01 MOTORS
Single phase motors shall be oil filled, permanent split capacitor, class B insulated NEMA B design, rated for continuous duty. At
maximum load the winding temperature shall not exceed 130 degrees C unsubmerged. Since air filled motors are not capable of
dissipating heat they shall not be considered equal. The pump motor shall have an integral thermal overload switch in the
windings for protecting the motor. The capacitor circuit shall be mounted internally in the pump.
6.01 BEARINGS AND SHAFT
Upper and lower ball bearings shall be required. The bearings shall be a single ball / race type bearing. Both bearings shall be
permanently lubricated by the oil, which fills the motor housing. The motor shaft shall be made of 300 or 400 series stainless steel
and have a minimum diameter of .311".
7.01 SEALS
The pump shall have a unitized carbon / ceramic seal with stainless steel housings and spring equal to Crane Type 6A. The motor
plate / housing interface shall be sealed with a Buna-N o-ring.
8.01 IMPELLER
The impeller shall be engineered polymer, with pump out vanes on the back shroud to keep debris away from the seal area. It
shall be threaded to the motor shaft.
9.01 CONTROLS
All pumps can be supplied with a CSA and UL approved VMF type switch, an integrally wired wide angle tilt float switch, or piggy
back type wide angle tilt float switches. The piggy back style switches are equipped with a plug that allows the pump to be
operated manually without the removal of the pump in the event that a switch becomes inoperable. Manual pumps are operable
by means of a pump control panel.
10.01 PAINT
The exterior of the casting shall be protected with Powder Coat paint.
11.01 SUPPORT
The pump shall have cast iron support legs, enabling it to be a free standing unit.
12.01 SERVICEABILTY
Components required for the repair of the pump shall be shipped within a period of 24 hours.
250_P5 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
background image
13.01 FACTORY ASSEMBLED TANK SYSTEMS WITH GUIDE RAIL AND QUICK DISCONNECT DISCHARGE
______ Guide factory mounted rail system with pump suspended by means of bolt on quick disconnect which is sealed by means
of nitrile grommets or o-rings. The disconnect system shall have an internal ball check. The Discharge piping shall be schedule
80 PVC and furnished with a PVC shut-off ball valve. The Tank shall be wound fiberglass or roto-molded plastic. A cast iron inlet
hub shall be provided with the fiberglass systems.
______ Stainless steel Guide Rail
______ Zinc plated steel Guide Rail
______ "diameter of basin size
______ "height of basin size
______ "distance from top of tank to discharge pipe outlet
______ Fiberglass cover
______ Structural foam polymer cover
______ Steel cover
______ Simplex System with Outdoor panel and alarm
______ Duplex System with Outdoor panel and alarm
______ Separate Outdoor Alarm
______ Remote Outdoor Alarm
14.01 TESTING
The pump shall have a ground continuity check and the motor chamber shall be Hi-potted to test for electrical integrity, moisture
content and insulation defects. The motor and volute housing shall be pressurized, and an air leak decay test is performed to
ensure integrity of the motor housing. The pump shall be run, voltage current monitored, and the tester checks for noise or other
malfunction.
15.01 QUALITY CONTROL
The pump shall be manufactured in an ISO 9001 certified Facility.
16.01 WARRANTY
Standard limited warranty shall be 2 years.
250_P6 R7/15/2008 ©Copyright 2008 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.